RESEARCH DOSSIER
Battery Energy Storage Thermal Runaway and Fire Risk Engineering
Abstract. Stationary lithium-ion battery energy storage systems combine concentrated electrochemical energy with electrical equipment, thermal management, digital control, environmental exposure, and shared infrastructure. This monograph investigates thermal runaway, propagation, combustible and toxic gas release, fire and explosion consequences, installation siting, protective functions, emergency planning, and the translation of engineering failures into insured and total economic loss. It integrates experimental literature, official incident investigations, institutional safety guidance, and publicly accessible standards scopes through a comparative engineering and insurance analysis. The Surprise, Liverpool, and Elkhorn incidents illustrate distinct escalation pathways and the evidentiary limitations of accident comparisons. An explicitly hypothetical conditional event tree demonstrates the sensitivity of expected damage and contract-limited indemnity to propagation and site-spread assumptions. The analysis emphasizes configuration-specific test validity, common-cause impairment, functional dependencies, evidence quality, and the distinction between physical containment and financial recovery. It develops original analytical synthesis without claiming a new theory, newly estimated loss frequencies, or universal installation design parameters.
Keywords: battery energy storage systems; thermal runaway; fire risk engineering; propagation; combustible gas; explosion hazards; fire protection; operational technology; insurance; loss prevention; emergency planning; business interruption.
Foundations and Definitions
Stationary battery energy storage systems (BESS) transform electrical energy across time. Their principal hazard is that a large inventory of electrochemical energy is concentrated in equipment whose normal operation requires close control of temperature, voltage, current, and the integrity of component interfaces. A fire-risk investigation therefore begins with the functional configuration of the installation rather than with its aggregate energy capacity alone. Two plants of the same nameplate capacity can have substantially different loss potential because the arrangement of cells, intermediate barriers, auxiliary equipment, and physical separation changes the pathways available for failure.
Thermal runaway is a self-accelerating exothermic process within a cell when heat generation exceeds effective heat removal and initiates additional reactions. Propagation is the transition from an initiating cell or component to additional cells, modules, racks, or equipment. Gas release, external flame, deflagration, and subsequent ignition are distinct phenomena. A damaged cell may vent combustible and toxic products even when no visible flame is present. An external fire can also initiate battery failure. The engineering object of this dossier is the relationship among these transitions and the barriers that interrupt them.
A grid-connected lithium-ion BESS normally includes cells, modules or other cell assemblies, racks or integrated cabinets, a battery management system (BMS), power-conversion equipment, electrical protective devices, supervisory controls, thermal-management equipment, and supporting electrical infrastructure. Containerized layouts are common but do not define BESS technology. Building installations, outdoor cabinets, and integrated equipment differ in confinement, access, ventilation, and fire exposure. The conclusions developed here principally concern stationary lithium-ion electrochemical storage; they are not generalized to flow batteries, sodium-sulfur systems, or other storage technologies without a separate hazard analysis.
Electrical power in megawatts (MW) measures the rate of delivery or absorption of energy. Electrical capacity in megawatt-hours (MWh) measures stored or deliverable electrical energy under specified conditions. One MWh equals 3.6 GJ of electrical energy. This conversion is not a battery fire calorimetry result: chemical reaction energy, combustion of materials, ventilation, and energy dissipated or retained during failure influence the actual heat released. Neither nameplate MW nor MWh alone measures the thermal consequences of an incident. Insured values and business interruption exposure introduce further dimensions that cannot be inferred directly from either quantity.
A useful engineering distinction is between initiating-event prevention, limitation of propagation, protection of exposed property, stabilization of incident conditions, and recovery. Each has different evidence requirements. A cell qualification test may support an inference concerning one stage; a property insurer needs evidence addressing the entire credible loss pathway. The governing analytical question is how an initially localized defect becomes a spatially extended, temporally persistent, and economically material event.
History and International Practice
The growth of grid-scale storage has made reliability and fire safety joint conditions of successful energy infrastructure development. Storage performs functions such as energy shifting, balancing, and support of electricity-network operation. These useful functions impose varying electrical and thermal duty cycles. High utilization can increase exposure to some degradation mechanisms, while operation within well-characterized conditions and effective thermal management can improve the predictability of system behavior. A scientifically defensible assessment therefore considers the actual service profile as well as the equipment's rated characteristics.
The historical development of stationary storage safety can be understood as a movement from component qualification toward installation-level assurance. A cell's electrochemical properties remain important, but a large installation creates additional interactions among electrical, mechanical, digital, and civil engineering systems. The United Kingdom government's 2024 grid-scale storage safety study situates safety across the project life cycle and distinguishes the roles of design, development, operation, and end-of-life management in controlling hazards. Its research scope and recommendations are informative beyond the UK, subject to differences in legal obligations and site conditions.
In international comparison, prescriptive codes, consensus test methods, performance-based engineering, regulator oversight, insurer loss-prevention guidance, and emergency-service planning have different institutional functions. Compliance with one document cannot be treated as a transferable guarantee of compliance with all others. Certification, test evidence, approval of plans, and actual operational performance represent distinct forms of assurance.
The international scope of the present work lies in its comparative treatment of engineering mechanisms and evidence, supplemented by US, UK, and international standards sources. It does not attempt a complete jurisdiction-by-jurisdiction survey. Local adoption dates, code modifications, permit conditions, public authority requirements, and contractual provisions must be established for any particular installation.
Physical and Causal Mechanisms
Electrochemical cells store energy through a controlled difference in chemical potential. During ordinary service, electrochemical reactions and resistive losses generate heat, which must be removed or accommodated within design limits. Damage, manufacturing defects, electrical abuse, environmental exposure, or abnormal thermal conditions can disrupt this balance. Feng et al. (2018), in their thermal runaway mechanism review, organize the physical pathways around interactions between abuse conditions, internal faults, and exothermic reactions. Their vehicle-focused review is relevant to mechanisms in stationary lithium-ion cells but does not supply stationary installation failure rates.
An elementary lumped heat balance can be expressed as C(dT/dt) = Q_gen − Q_out, where C is effective heat capacity in joules per kelvin, temperature T is in kelvin, and both heat rates are in watts. Q_gen may depend nonlinearly on temperature, reaction progress, state of charge, and electrical conditions; Q_out depends on the thermal connection to surrounding materials and the environment. When the production of heat grows more rapidly than its removal, an initially limited temperature rise can accelerate. A bulk-temperature approximation is appropriate only where its treatment of spatial gradients is defensible. Internal hot spots and transient thermal contact can invalidate it even when the average measured temperature appears comparatively modest.
The distinction between measured casing temperature and local internal temperature has important consequences. The sensing location, thermal inertia, sensor availability, and sampling characteristics affect when abnormal heat generation becomes observable. A temperature alarm is evidence of conditions at a particular sensing location; the absence of an alarm does not by itself establish the absence of cell-level degradation. Independent electrical diagnostics and trend analysis help characterize uncertainty before obvious overheating occurs.
Cell chemistry influences thermal stability, reaction pathways, gas generation, and heat release, but a chemistry label alone cannot predict installation-scale risk. Electrode formulations, cell construction, geometry, electrolyte, state of charge (SOC), aging, and abuse history alter the conditions under which the cell fails. Lithium iron phosphate and nickel-rich layered-oxide families differ in important characteristics. Their comparative installation risk nevertheless depends on the complete design and exposure. A favorable cell-level characteristic must be connected to test evidence for the relevant pack and installation configuration before credit is assigned to it.
Thermal runaway propagation involves heat transfer by conduction, convection, radiation, and movement of hot gases or expelled material. Feng et al. (2015), in a large-format module propagation experiment, investigated a particular module architecture and found that thermal conduction through cell shells was consequential in the tested arrangement. This finding illustrates why interface geometry and thermal pathways are central to propagation assessment. It is not a universal ranking of heat-transfer mechanisms for other cell forms or module layouts.
Energy distribution during failure can include heat retained in the cell casing, hot expelled material, and changes in surrounding components. The National Laboratory of the Rockies' Battery Failure Databank provides experimental approaches for studying these distinctions, including measurements of mass and heat associated with ejecta and cell bodies. The database is valuable for designing comparisons of cell behavior. The present dossier did not download and statistically analyze its underlying experimental records; no new distributional estimate is asserted.
A cell that has already crossed the point of self-sustaining decomposition may continue generating heat after electrical connection is interrupted. Isolation remains valuable because it can prevent additional electrical input, limit collateral faults, and support other protection functions. Its effectiveness depends on what has already occurred physically. Treating electrical isolation as equivalent to the immediate termination of every exothermic reaction would overstate what this barrier accomplishes.
Gas Release Fire and Explosion
The release of gases creates an additional hazard pathway whose consequences depend on transport, mixing, confinement, ignition, and exposure. Thermal runaway can produce combustible and toxic products; an enclosure containing a failed battery may therefore develop hazardous atmospheric conditions even during an apparent pause in visible combustion. A fire investigation that treats smoke, atmosphere, and flame as interchangeable indicators cannot reliably distinguish the relevant states.
Larsson et al. (2017), in their fluoride gas emissions experiments, measured hydrogen fluoride emissions in externally initiated fire tests involving multiple battery types. The reported range of 20–200 mg per Wh of nominal capacity describes the tested conditions. It is neither a universal emission factor nor a basis for multiplying site-wide installed capacity to estimate a real atmospheric concentration. Exposure assessment additionally requires the fraction of inventory involved, time-dependent source terms, release locations, ventilation, meteorology, dispersion, chemical interaction, and receptor characteristics.
The difference between combustible release and explosion is equally important. Combustible gas accumulation creates a potential for combustion; the resultant pressure effects depend on actual concentration distributions, ignition, enclosure geometry, congestion, and pressure-relief characteristics. The spatial variability of atmospheric conditions means that a single monitoring location cannot establish uniform safety across an enclosure. Measurements must be interpreted within the verified limitations of instruments and sampling arrangements.
Ventilation is an engineered function with multiple objectives. It can influence the accumulation of combustible gases, the transport of smoke, and the transfer of heat. It can also affect the oxygen available for combustion and the movement of hazardous products toward receptors or equipment. Consequently, a ventilation design must be evaluated against credible event states, loss of electrical supply, sensor failure, adverse environmental effects, and its interactions with other safety functions. The correct engineering question is whether the installed system controls the specific conditions for which it is designed, with performance evidence appropriate to that claim.
Detection, ventilation, explosion protection, suppression, and structural separation are complementary controls. Their combined effectiveness is a function of response time, availability, independence, and the compatibility of the design assumptions. Specific design setpoints, vent dimensions, and emergency operating sequences require site-specific evaluation by qualified personnel under applicable requirements. This monograph establishes the analytical relationships rather than furnishing construction or emergency-response instructions.
Exposure and Failure Modeling
Exposure is the extent to which an installation, its occupants and surroundings, and its financial stakeholders are subject to the consequences of hazardous events. A useful exposure inventory includes stored energy, component populations, operating duty, installed equipment values, layout, neighboring assets, fire compartment boundaries, environmental receptors, network function, key suppliers, and restoration dependencies. The exposure unit must correspond to the question being studied.
Risk can be represented as a distribution of possible outcomes conditional on identified initiating events and subsequent barrier performance. In an event tree, the probabilities of branches are conditional on the preceding states. Treating them as unconditional quantities or assuming independent failures of protective systems without evidence leads to false precision. A BMS fault, loss of auxiliary supply, flooding, or incorrect software change can simultaneously affect several barriers, so the same common cause must be represented only once in a properly structured analysis.
A conventional illustrative event tree provides a transparent way to examine the financial implications of propagation. Assume, solely for illustration, an initiating-event frequency of 0.04 per site-year; a conditional probability of propagation of 0.20; and a conditional probability of site spread given propagation of 0.10. Assign direct monetary damage of USD 0.15 million when propagation does not occur, USD 2 million when propagation remains limited, and USD 20 million when site spread occurs. These parameters are hypothetical, not estimated from the incident literature.
The three conditional branch probabilities are respectively 0.80, 0.18, and 0.02. Their sum is one. Expected damage per initiating event is 0.80 × 0.15 + 0.18 × 2 + 0.02 × 20 = USD 0.88 million. Multiplication by the assumed frequency gives USD 35,200 per site-year in expected damage. If the conditional probability of site spread rises from 0.10 to 0.30 while the other inputs remain fixed, the corresponding branch probabilities become 0.80, 0.14, and 0.06. Expected damage per event rises to USD 1.60 million, and annual expected damage rises to USD 64,000.
This example identifies a practical consequence of the distribution of loss: a relatively infrequent escalation pathway can dominate changes in expected damage. It does not establish an empirically calibrated BESS loss model, and it omits distinct atmospheric-explosion, third-party liability, and interruption consequences. It also assumes a stationary event frequency and uses deterministic branch severities. A production insurance model would require loss distributions, dependence structures, explicit coverage treatment, exposure evolution, and validation against suitable data.
For independent homogeneous Poisson events, observing zero events during T site-years gives a one-sided approximate 95% upper frequency bound of 3/T, obtained from −ln(0.05)/T. The result illustrates why a short failure-free operating record provides weak evidence about rare loss frequency. Such inference requires a well-defined cohort, complete observation, comparable exposure, and justified assumptions about stationarity and independence. A changing fleet with different equipment generations and reporting practices generally requires a more careful model.
Risk assessment must separate aleatory variation, which is represented as randomness conditional on the model, from epistemic uncertainty about parameters, physical mechanisms, and the structure of the model itself. Sensitivity analysis should alter credible inputs and alternative assumptions, including correlations and barrier unavailability, rather than simply presenting a narrow arithmetic uncertainty band around an unvalidated central estimate.
Siting and Spatial Loss Control
Site layout determines the pathways through which a battery incident can expand beyond its initiating assembly. The relevant spatial relationships include the position of adjacent cabinets, buildings, power-conversion equipment, transformers, cable routes, access corridors, property boundaries, and sensitive environmental receptors. Surrounding features can alter fire exposure and the practical ability of responders to assess or stabilize conditions.
The site development process should account for flood susceptibility, drainage, topography, climate, external fire exposure, contamination and corrosive conditions, and the reliability of auxiliary infrastructure. Risk scenarios should include the possibility that an environmental event affects multiple cabinets or shared utilities simultaneously. Physical separation cannot fully compensate for a common vulnerability that arises elsewhere in the system. Conversely, reducing dependencies can retain the benefits of local containment even when a particular unit is lost.
The NFCC's 2025 storage system planning guidance provides a fire-service perspective on planning and emergency access, with attention to site-specific conditions, water and runoff, and coordination. FM's 2026 energy storage loss-prevention data sheet addresses property-protection measures for relevant stationary installations. Both contribute to engineering judgments; their recommendations have distinct institutional purposes and should be interpreted in their applicable scope.
Separation distances should be assessed using credible exposure scenarios and relevant evidence, including thermal radiation and other routes by which equipment can be affected. A test that establishes limited propagation within one installation design does not automatically support the same distance under different orientations, openings, shielding, or weather conditions. Physical similarity must be established for the aspects that govern the claim.
Loss boundaries should be described in terms of equipment and functions, not just spatial units. A fire confined to one enclosure can still interrupt a much larger system if it damages a shared electrical interface or triggers a prolonged investigation and reset. Siting decisions consequently influence physical protection, equipment serviceability, replacement logistics, and the duration of disruption. Effective property protection is closely related to the ability to restore unaffected assets without compromising safety.
Intervention and Assurance
The principal prevention objective is to keep cells and electrical equipment within operating conditions established by the design and validated for foreseeable disturbances. Prevention encompasses materials and manufacturing quality, protection against mechanical and environmental damage, electrical coordination, thermal management, operational controls, inspection, and safe handling of faults throughout the operating life. These measures can reduce initiating-event frequency before propagation becomes relevant.
Early detection supports intervention only when the indication arrives in time, is interpreted correctly, and reaches an available protective function. Tam et al. (2026), in their heat interruption experiments, report that intervention windows varied among tested cell formats and conditions. The accessible abstract supports the conditional character of early intervention, not a universal timing threshold. A risk engineer should therefore examine the evidence linking detector response to the kinetics of the relevant failure scenario at the actual system scale.
Passive barriers aim to limit energy transfer and exposure without requiring a correctly timed control action. Their effectiveness depends on material properties, installation quality, contact geometry, openings, aging, and the conditions to which they are subjected. Active systems provide potentially adaptable protection but depend on available sensing, power, control logic, and actuation. Both types require methodical assurance. A barrier's designation as passive or active is a starting point for reliability analysis, not an intrinsic quantitative rating.
Fire suppression and cooling serve different but overlapping functions. External suppression can address combustion and cooling can reduce heat transfer to exposed equipment, depending on the configuration and agent application. Inaccessible internal cell reactions may persist. The property-protection recommendations in FM Data Sheet 5-33 (2026) reinforce the importance of understanding the actual purpose and limitations of protection in a BESS environment. Claims that a system extinguishes cell thermal runaway, prevents every explosion, or ensures safe reentry require evidence beyond the mere presence of suppression equipment.
Commissioning is a demonstration that the installed design and its safety functions satisfy defined requirements. Relevant assurance includes as-built configuration review, traceability of component and firmware versions, verification of safety function interactions, and documentation of the conditions under which protective systems are effective. Testing of alarm transmission and the handling of safety-system impairments should form part of a maintained operating assurance process. The purpose is to reveal discrepancies between documentation and actual installation before those discrepancies become accident contributors.
Maintenance should identify and follow changes affecting the original risk assessment. Replacement cells, changes in firmware, alternate suppliers, enclosure modifications, thermal-management changes, and modifications to control interfaces can invalidate assumptions of previous tests. A change-control process must distinguish functionally equivalent replacements from changes with new risk implications. A commissioning record remains useful evidence only while the design and operating conditions to which it refers remain relevant.
Digital and Electrical Protection Dependencies
Modern storage installations couple electrical equipment with digital supervisory functions. The BMS monitors and controls battery parameters, while energy management and supervisory systems coordinate the operation of the wider installation. Communication interfaces connect local equipment to plant controls and potentially to external operating or maintenance platforms. These relationships create both opportunities for earlier fault identification and potential pathways for failure.
A protective function should be evaluated from measurement through interpretation, communication, decision, actuation, and verification of its result. A locally detected abnormal condition may be lost at an interface, assigned an inappropriate priority, or fail to cause the intended operational response. Effective indication is therefore a property of the complete signal and decision chain. A dashboard capable of displaying a warning is insufficient evidence that the corresponding safety action operates reliably.
Stouffer et al. (2023), in NIST’s operational technology security guide, describe security considerations appropriate to systems whose operation affects physical processes and safety. In a BESS installation, cybersecurity and conventional reliability can intersect through availability, unauthorized configuration changes, misleading indications, and the integrity of control interfaces. This does not imply that any investigated battery fire was caused by a cyberattack. The appropriate inference is that integrity and availability of the digital control architecture belong within physical risk assurance.
The distinction between ordinary control and independently assessed protection is important wherever a common fault can undermine both. Independence is a claim about dependencies in hardware, software, power, sensors, communication, and organizational authority, rather than a label assigned to a subsystem. Credible common-cause vulnerabilities should be examined before multiplying barrier success probabilities.
Electrical design also influences fault localization and the consequences of isolation. Protection coordination, component integrity, and the implications of shared electrical systems should be established by qualified electrical engineering review. A safety assessment should connect an interrupted electrical path to its actual effect on stored electrochemical energy, adjacent equipment, and the wider installation. It must avoid assuming that a remote command alone establishes a physically safe state.
Documentation of operating events is an additional protective resource. Time-synchronized logs, configuration history, alarm records, and retained fault information support root-cause investigation and corrective maintenance. Where critical telemetry is unavailable after an incident, even the distinction between initiating fault and subsequent consequence may become uncertain. Evidence preservation is therefore part of both risk engineering and insurance claims investigation.
Emergency Planning and Environmental Consequences
An emergency plan connects technical knowledge of the facility to the institutions and personnel who may encounter an incident. It should be developed with the applicable fire and rescue authorities, site operators, emergency management personnel, and other necessary stakeholders. The plan has value only when the relevant information can be obtained, interpreted, and used under the conditions of a real event.
Important planning subjects include the physical configuration of the site, the nature of the stored energy, system isolation arrangements, limitations of remote indications, possible persistent hazards, safe access considerations, environmental receptors, communication responsibilities, and post-incident control. The appropriate response is determined by trained incident command in accordance with site-specific plans and applicable authorities. This research does not prescribe firefighting tactics, reentry criteria, gas concentration limits, or field actions.
The institutional lessons of the 2019 Arizona incident are described by McKinnon et al. (2020) in their Surprise explosion investigation. The case underscores the importance of information about the atmosphere and evolving conditions, explosion-related hazards, and specialist training. It demonstrates that the absence of visible active flame is a weak basis for conclusions about the safety of an enclosure following battery failure.
The protection of people and the environment may require consideration of exposure beyond the immediate asset. Smoke and other releases can affect nearby communities; contaminated water and damaged materials can complicate incident management and recovery. Evaluation should consider credible pathways and receptors rather than assigning universal quantities to every fire. The possibility of environmental impacts does not establish their magnitude at any specific incident.
Post-incident stabilization and recovery are part of the overall consequence analysis. Damaged battery equipment may have uncertain residual energy and altered structural or electrical integrity. Documentation, specialist recovery arrangements, and coordination with responsible authorities are required for the management of affected equipment and wastes. An insurer's interest in rapid loss mitigation does not displace safety responsibilities or justify premature return to operation.
Empirical Evidence and Research Method
This study uses a targeted comparative literature review of experimental battery research, official incident reports, institutional guidance, standards catalog records, and regulatory communication. Sources were selected for relevance to physical mechanisms, propagation, protective functions, emergency management, and insurance interpretation. It is a qualitative evidence synthesis with an explicitly hypothetical numerical sensitivity example. It is not a systematic review with an exhaustive search protocol, an independent test program, or an actuarial estimation of BESS failure frequency.
Evidence from controlled cell experiments is valuable because boundary conditions can be specified and measured. Its weakness for installation risk is external validity: equipment configurations, scale, confinement, and operation may differ materially. Module and installation tests address additional physical interactions but are still conditioned on specimen selection, initiation method, environmental conditions, instrumentation, and test objectives. Operational incident records bring real-world complexity while generally offering less experimental control and variable causal documentation.
EPRI's (2024) failure root-cause analysis describes 81 incident entries, of which 26 could be classified in terms of both root cause and failed element under the report's approach. The resulting proportion, approximately 32.1%, is a measure of classifiability for that database snapshot. It is not an estimate of the probability of a particular initiating fault in the entire deployed fleet. The report also describes a 97% reduction in reported incident rate normalized to deployed GW between 2018 and 2023. The normalization and reporting limitations mean that this observation cannot be converted directly into a site-year probability or into an insured-loss frequency.
The data needed for stronger inference include the installed cohort, operating start and end dates, power and energy capacity, equipment configurations, operating duty, reporting criteria, component changes, safety controls, and verified loss information. Denominator choice is important. Installed GW, installed GWh, site-years, cabinet-years, and energy throughput measure different kinds of exposure. Comparing rates computed on different denominators without reconciliation may generate apparently conflicting trends even when the underlying incidents are the same.
Reporting is often conditioned by severity, public visibility, regulatory obligations, and access to incident information. Some of the most informative near misses may never appear in public datasets. Changes in reporting expectations and the growing maturity of investigation practice can alter the observed time series. In addition, the population at risk changes as equipment generations enter and leave service.
The appropriate approach for engineering comparison is a structured source record specifying what was observed, what was inferred, the authors' stated limitations, and the relationship of those findings to the claim being tested. The evidence ledger accompanying this monograph distinguishes full text or relevant passages examined from abstracts and catalog scopes. It records the limited access to paid standards; no detailed mandatory provisions from an unexamined full standard are asserted.
Standards Regulation and International Comparability
Standards and regulatory requirements provide institutional mechanisms for translating engineering knowledge into design, installation, and operating expectations. They must be interpreted by edition, authority, technical scope, and jurisdiction. A test method specifies how evidence is generated for its defined purpose; a system safety standard addresses a broader set of requirements; an installation standard concerns how equipment is placed and used. These functions cannot be collapsed into a single certificate.
The public scope of ANSI/CAN/UL 9540A:2026 identifies the sixth edition of a test method for thermal runaway fire propagation in BESS. Its official catalog was examined, but its complete normative text was not available for review. UL Solutions' large-scale fire testing explanation describes relationships among UL 9540A, UL 9540, and NFPA 855 and explains the evolving installation-scale testing approach. The explanation identifies January 1, 2027, as an announced effective date associated with the sixth-edition transition. This does not establish that every jurisdiction has adopted that edition or that every existing facility must meet identical requirements.
A test report should be evaluated by the specific edition and configuration tested, the exposure conditions, the data generated, and the engineering conclusion for which the report is offered. A claim about a particular installation requires sufficient correspondence between the tested and actual design. Where the configuration differs materially, qualified review is needed to determine the applicability of the existing evidence or the need for additional analysis.
The public scope of IEC 62933-5-2:2025 addresses safety requirements for grid-integrated electrochemical energy storage systems. Its international relevance lies in treating safety within the interactions of an integrated system and its life cycle. The full paid text was not examined, and this monograph makes no clause-level compliance determination. International publication of a standard does not itself determine the legal obligations applicable at any particular site.
The United States provides an example of jurisdiction-specific oversight through the California Public Utilities Commission's 2025 battery storage safety announcement, which describes adopted changes to General Order 167-C and enhanced emergency-planning oversight. Its scope is California's regulatory setting. The United Kingdom government research and fire-service guidance represent a different institutional setting, combining technical analysis and planning practice. Insurer guidance, including FM property-loss-prevention recommendations, has a further distinct role that can be incorporated into contracts or engineering requirements where the parties so provide.
For underwriting, these distinctions require an evidence matrix rather than a binary question about whether an installation is compliant. The matrix should identify each relevant obligation or engineering objective, its source and edition, the equipment to which it applies, the evidence of conformity, the status of exceptions or changes, and the remaining uncertainty. The insurer must distinguish documentary assurance from independent engineering verification and must not represent an engineering opinion as a legally binding compliance determination.
Comparative Incident Studies
The following incidents illustrate variation in failure pathways, response challenges, and observed consequences. They were selected for the availability of source documentation and for contrasting analytical value. They are not a representative sample of BESS losses or an empirical ranking of technologies.
At Surprise, Arizona, on April 19, 2019, an incident involving a 2.16 MWh installation developed into a cascading battery failure and deflagration that injured four firefighters. The official investigative report by McKinnon et al. (2020) addresses the event and the implications for monitoring, explosion protection, and responder safety. The central interpretation here is that the progression from battery failure to an atmospheric explosion was a distinct escalation pathway with consequences separate from direct battery damage. The precise ignition mechanism is not asserted beyond the report's evidentiary scope.
The Carnegie Road installation in Liverpool experienced a fire on September 15, 2020. The Merseyside Fire & Rescue Service's post-incident safety update describes changes following its recommendations, including information availability, alarms, access, water management, and evacuation planning. The source documents institutional learning and reported improvements. It does not provide independent quantitative proof of the resulting change in loss probability. The case is useful because it links the physical configuration of an installation with planning information and organizational coordination.
The Elkhorn incident of September 20, 2022, is documented in the Energy Safety Response Group's 2023 Elkhorn technical findings. The report describes evidence linking water intrusion, the displacement of valves associated with enclosure modifications, and electrical short circuits, with shortcomings involving safe-discharge functionality and escalation of indications. The 182.5 MW/730 MWh facility suffered the total loss of one affected Megapack and minor cosmetic damage to neighboring equipment, according to the report. The findings concern this identified facility and incident; they should not be conflated with other incidents in the Moss Landing area.
The Elkhorn case demonstrates both the significance of an environmental and configuration-related initiating pathway and the possibility of a comparatively localized physical loss within a much larger installed capacity. It also illustrates why an evaluation of safety architecture should examine modifications, signal handling, and protection functionality together. The case cannot establish that the same containment outcome would follow from all possible initiating events or at other installations.
Comparing the three incidents clarifies a fundamental distinction. Incident initiation concerns the conditions that bring a component or system into failure; escalation concerns the pathways through which that failure becomes a larger hazard; the loss outcome concerns the assets, people, and functions ultimately affected. An investigation may produce strong evidence about one of these levels and weak evidence about another. A comparative study should preserve these differences rather than assign each event a single explanatory category.
The cross-case engineering implication is that neither the presence of a BMS nor the nominal fire resistance of a unit constitutes sufficient assurance for all scenarios. Physical propagation control, the management of gas-related hazards, environmental integrity, digital protection, and institutional response require separate evidence and evaluation of their dependencies. The cases support the need for these analyses without providing numerical probabilities for their failure.
Insured and Total Economic Loss
The total economic loss from a BESS incident can comprise damage to battery equipment and supporting infrastructure, restoration expenditure, interruption of operations, additional purchased services, contractual consequences, third-party losses, and environmental management costs. Insurance transforms parts of that economic loss into an indemnity or other contractually specified payment. The transformation depends on contract terms, applicable law, valuation, exclusions, deductibles, limits, sublimits, and the facts of the event.
Physical damage to a battery unit should be distinguished from the cost of replacing a wider system, including unaffected equipment whose compatibility, certification, or availability becomes an issue during recovery. Replacement cost depends on equipment specifications, supplier capacity, transport, installation, integration, and recommissioning. A technically contained event can produce significant business interruption if a shared electrical connection or operating approval prevents service restoration.
Property and machinery-related insurance questions may overlap because an initiating electrical or mechanical failure can lead to fire and damage to surrounding property. The applicable insurance treatment requires examination of the relevant policy and causal facts. Construction-stage, operational-stage, liability, and environmental coverage may have different terms and triggers. The existence of an engineering hazard does not establish that a particular financial consequence is insured.
The earlier illustrative event tree can be used to demonstrate the effect of simple indemnity terms. Suppose an otherwise fully covered occurrence is subject to a USD 0.1 million deductible and a USD 5 million per-occurrence limit. If L denotes the branch damage in millions of dollars, the illustrative payment is min(5, max(L − 0.1, 0)). This assumes no other conditions, exclusions, or aggregation complications. The expected payment per initiating event is 0.80 × 0.05 + 0.18 × 1.9 + 0.02 × 5 = USD 0.482 million; the assumed annual frequency gives USD 19,280 per site-year. Neither result is a premium quote, loss estimate for an actual plant, or recommendation for contract limits.
The difference between expected physical damage and expected payment illustrates how contractual boundaries transform the loss distribution. Deductibles primarily affect smaller payments in this example, whereas the limit truncates the more severe branch. Technical risk reduction should therefore be evaluated using both total consequence and contract-specific insured consequence. A decision that reduces only the uninsured part of an extreme loss can still materially improve safety and economic resilience.
Portfolio risk introduces additional relationships. Insurers may cover installations sharing equipment generations, suppliers, control components, environmental exposures, or restoration dependencies. Common vulnerabilities can make losses dependent even when the physical sites are geographically dispersed. Reinsurance and accumulation management require consistent asset identifiers, coverage definitions, vulnerability information, and the treatment of common causes. Simple accumulation of nameplate energy capacity is an incomplete surrogate for these relationships.
Claims investigation should document the incident chronology, origin and cause evidence, damaged and exposed property, mitigation expenditure, operational interruptions, and restoration alternatives. The engineering findings and coverage interpretation should remain distinguishable in the claim record. Evidence of a defect, operational weakness, or modification does not by itself establish the contractual or legal allocation of responsibility.
Underwriting and Risk Engineering Application
A defensible loss survey begins by identifying the insurance exposure and the scientific boundaries of the engineering assessment. The survey should establish equipment identity, system architecture, location and external hazards, relevant test records, operating conditions, protection functions, maintenance arrangements, emergency planning, and plausible interruption scenarios. Its task is to develop a well-supported account of residual risk rather than simply tally the presence of nominal safety features.
Evidence quality is central to the evaluation. Manufacturer documentation may establish design intent; a witnessed test can establish performance within the tested conditions; commissioning evidence can address the actual installation; maintenance records can support continuing availability; incident experience can reveal previously unrecognized pathways. The strongest assessment integrates these forms of evidence rather than treating any single one as universally decisive.
Underwriting questions concerning protection reliability should distinguish between the existence of a safety function, the evidence that it operates correctly, and the assurance that it remains available over the policy period. Protection impairment procedures, management of change, and evidence of corrective action can be financially relevant because they influence uncertainty about future barrier availability. Such information has different evidentiary weight from unsupported statements about general technology quality.
The insurer should also identify the assumptions behind a maximum-loss or credible severe-loss scenario. The assessment may need to consider loss of a unit, damage to multiple units, exposure of adjacent property, simultaneous impairment of shared controls, and prolonged interruption. A selected loss scenario is conditional on its assumptions about event development and available protection. Presenting it as an absolute upper bound without justification risks understating extreme loss.
An improvement recommendation must be connected to a specific hazard or consequence and expressed in a manner that allows evidence of completion to be assessed. Recommendations concerning compliance, certification, design modification, or response planning should identify the appropriate competent parties. The risk engineer's role is to connect evidence about prevention and limitation of damage to the exposure being insured; the determination of contractual requirements and the engineering of physical systems remain distinct responsibilities.
A change in an underwriting estimate should be traceable to the reasons for that change. Improved testing evidence, reduction of shared vulnerabilities, better understanding of interruption dependencies, or a revised loss scenario can affect the evaluation. Changes in market conditions or insurance capacity may affect pricing without representing a physical change in the installation. Maintaining these distinctions improves the interpretation of both engineering and financial assessments.
Uncertainty and Counterfactual Analysis
The central difficulty of causal evaluation in a complex installation is that the consequences of preventive measures are often unobserved. If a fire remains confined, the result could reflect the effectiveness of one barrier, the combined action of several barriers, a favorable initiating scenario, or other circumstances. If an incident occurs despite the presence of protection, the result does not establish that the protection provided no benefit. Scientific assessment must identify the comparison implied by a causal claim.
Counterfactual analyses can use matched tests, physically plausible simulation, and comparisons of configurations under specified conditions. They should state which factors are held constant, which are changed, and the reasons that the comparison is appropriate. The results of a controlled experiment support an inference within its validated boundary; extrapolation to differently configured equipment requires an independent argument.
The costs and benefits of a protective intervention can also be sensitive to the distribution of outcomes. In the numerical example, an increase in the probability of severe spread substantially changes expected loss even though the initiating frequency is held fixed. The inverse relationship implies that mitigating escalation can be economically valuable under certain exposure conditions. The actual value depends on the empirically supported effect of the measure, residual severity, implementation costs, reliability, risk tolerance, and contract terms.
Uncertainty in fire consequence assessment includes uncertainty about the source term, equipment involvement, heat-transfer conditions, gas movement, weather, and exposure consequences. Model validation should focus on relevant physical observables and limitations rather than only on agreement with an aggregate loss outcome. Multiple models might reproduce one incident while predicting different behavior for another scenario. Investigators should preserve alternative explanations where observations cannot distinguish them.
An especially consequential uncertainty concerns future equipment and operational changes. A loss rate measured for one fleet generation or environment may not transfer to later technology, while lessons concerning organizational and physical dependencies may remain relevant. The evidence should therefore be periodically reassessed for applicability, with the reasons for any transfer or non-transfer expressly documented.
Conclusion
Battery energy storage thermal runaway is a physical process embedded in an engineered installation and institutional operating environment. The significance of thermal runaway for insurance arises from the potential of that process to spread across equipment, generate hazardous atmospheres, impair surrounding assets, and interrupt valuable operations. Establishing the initiating mechanism alone cannot determine the magnitude of the resulting loss.
This study's analytical contribution is to relate established heat-transfer, propagation, control-reliability, and event-tree concepts to the boundary between physical damage and insured loss. It identifies the importance of conditional escalation probabilities, installation-specific test applicability, common dependencies among protective functions, and the relationship between physical containment and financial interruption. The hypothetical example demonstrates these relationships arithmetically; it supplies no newly estimated industry parameter. The contribution is an integrated interpretation of existing evidence and methods.
The most consequential findings for risk engineering are that cell-level evidence requires an explicit basis for transfer to an installation, gas and explosion hazards require separate assessment from direct fire damage, and organizational and digital protective functions must be evaluated as complete operational chains. Credible property-loss scenarios should incorporate the spatial and functional dependencies of the installation. Insurance evaluation additionally needs to preserve the difference between total economic consequences and covered payments.
Future research should develop exposure-normalized incident cohorts with consistent reporting, configuration and operational metadata, and transparent classification of root causes and loss outcomes. Experimental research should investigate the transferability of results across equipment architectures and operating conditions, including the relationship between early detection and independently verified intervention outcomes. Installation-level studies should address dependencies among safety functions, recovery duration, and the performance of protective measures over time. Insurance-focused studies should connect verified engineering outcomes with consistently defined and suitably anonymized damage and interruption records.
The current evidence supports these research priorities and the analytical distinctions developed in this monograph. It does not establish a globally representative BESS fire frequency, a universal separation distance, a uniform insurance loss ratio, or a preferred battery chemistry for every installation. Those determinations require evidence specific to their physical, operational, legal, and economic context. The final engineering objective is the reduction of preventable loss through verifiable control of hazardous processes and a realistic account of the conditions under which those controls remain effective.
References
California Public Utilities Commission (CPUC) (2025). CPUC Sets New Safety Standards and Enhances Oversight of Emergency Plans for Battery Energy Storage Facilities. Regulatory announcement, March 13.
Department for Energy Security and Net Zero (2024). Health and safety in grid scale electrical energy storage systems. Research prepared by Frazer-Nash Consultancy, April 18.
Electric Power Research Institute (EPRI) (2024). Insights from EPRI’s Battery Energy Storage Systems (BESS) Failure Incident Database: Analysis of Failure Root Cause. White paper, product 3002030360, May.
Energy Safety Response Group (2023). Elkhorn Battery Energy Storage System Fire of September 20, 2022. Public Report of Technical Findings, Pacific Gas and Electric Company.
Feng, X., Ouyang, M., Liu, X., Lu, L., Xia, Y., & He, X. (2018). Thermal runaway mechanism of lithium ion battery for electric vehicles: A review. Energy Storage Materials, 10, 246–267.
Feng, X., Sun, J., Ouyang, M., Wang, F., He, X., Lu, L., & Peng, H. (2015). Characterization of penetration induced thermal runaway propagation process within a large format lithium ion battery module. Journal of Power Sources, 275, 261–273. DOI: 10.1016/j.jpowsour.2014.11.017.
FM (2026). Lithium-Ion Battery Energy Storage Systems. Property Loss Prevention Data Sheet 5-33, April interim revision; originally January 2017.
International Electrotechnical Commission (2025). IEC 62933-5-2:2025 Electrical energy storage (EES) systems - Part 5-2: Safety requirements for grid-integrated EES systems - Electrochemical-based systems. Official standard catalog and public scope.
Larsson, F., Andersson, P., Blomqvist, P., & Mellander, B.-E. (2017). Toxic fluoride gas emissions from lithium-ion battery fires. Scientific Reports, 7, 10018.
McKinnon, M. B., DeCrane, S., & Kerber, S. (2020). Four Firefighters Injured in Lithium-Ion Battery Energy Storage System Explosion - Arizona. UL Firefighter Safety Research Institute, July 28.
Merseyside Fire & Rescue Service (n.d.). Battery Energy Storage Site enhances safety in response to recommendations from MFRS. Official incident-related safety update.
National Fire Chiefs Council (NFCC) (2025). Grid scale energy storage system planning - Guidance for fire and rescue services. Planning guidance approved December 2025.
National Laboratory of the Rockies (n.d.). Battery Failure Databank. Research database and methodology.
Stouffer, K., Pease, M., Tang, C., Zimmerman, T., Pillitteri, V., Lightman, S., Hahn, A., Saravia, S., Sherule, A., & Thompson, M. (2023). Guide to Operational Technology (OT) Security. NIST Special Publication 800-82 Revision 3. DOI: 10.6028/NIST.SP.800-82r3.
Tam, W. C., Fang, H., Chen, J., Wang, Q., Brown, C., Emon, M., & Putorti, A. (2026). Examining safe intervention windows for 18650 and 21700 lithium-ion batteries under heat interruption experiments. Applied Thermal Engineering, article 131107. DOI: 10.1016/j.applthermaleng.2026.131107.
UL Solutions (n.d.). Understanding UL 9540A, NFPA 855 and Large-Scale Fire Testing for Battery Energy Storage Systems. Technical explanation of test-method and installation-standard relationships.
UL Standards & Engagement (2026). ANSI/CAN/UL 9540A:2026: Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems. Sixth edition, March 13; ANSI catalog and public scope.